Due to the large number of product configurations and associated optional switchover boxes, the following overview was created.
Always choose the switchover box based on the selected hybrid inverter. The battery connected to it is not relevant for the choice of box.
Do you need a switchover box?
- No switchover box is needed for backup power. Without a box, the inverter supplies whatever is connected to its backup power output.
- With a switchover box, whatever is connected to the box is supplied.
- You only need an FRT version if an additional PV inverter is installed on the output side of the box. The FRT capability of the hybrid inverter does not change the box. This also applies in Austria.
- neoom does not offer a switchover box for GoodWe systems.
Systems with SFI inverter
Name | Info | Max. grid connection | Backup power 100mA RCD integrated | FRT-capable? (for AT) | Part number | Link |
Switchover box SWIITCH 20 kW | Connection of 1 SFI 10 or 15 kW | 35A | Yes | No | 40811011 |
|
Incl. BEAAM & SMAART (installed) |
|
|
|
|
|
|
Switchover box SWIITCH FRT 20 kW | Connection of 1 SFI 10 or 15 kW | 35A | Yes | Yes | 40811012 |
|
Incl. BEAAM & SMAART (installed) |
|
|
|
|
|
|
Systems with NEEO inverters
Name | Info | Max. grid connection | Backup power 100mA RCD integrated | FRT-capable? | Part number | Link |
(for AT) |
|
|
|
|
|
|
Switchover box SWIITCH 20 kW | Connection of 1 NEEO 10, 15, or 20 kW | 35A | Yes | No | 40811003 | |
Incl. BEAAM & SMAART (installed) |
|
|
|
|
|
|
Switchover box SWIITCH FRT 20 kW | Connection of 1 NEEO 10, 15, or 20 kW | 35A | Yes | Yes | 40811004 | |
Incl. BEAAM & SMAART (installed) |
|
|
|
|
|
|
Switchover box SWIITCH 20 kW | Connection of 1 NEEO 10, 15, or 20 kW | 35A | Yes | No | 40800936 | |
incl. SMAART (installed) |
|
|
|
|
|
|
WITHOUT BEAAM |
|
|
|
|
|
|
Switchover box SWIITCH FRT 20 kW | Connection of 1 NEEO 10, 15, or 20 kW | 35A | Yes | Yes | 40800937 | |
incl. SMAART (installed) |
|
|
|
|
|
|
WITHOUT BEAAM |
|
|
|
|
|
|
Systems with Solax inverters (NEA)
Name | Info | Max. grid connection | Backup power 100mA RCD integrated | FRT-capable? | Part number | Link |
|---|---|---|---|---|---|---|
Switchover box up to 10kW_1WR | Connection of 1 Solax | 25A | No | No | 40500922 | |
Switchover box up to 20kW_2WR | Connection of 2 Solax | 35A | No | No | 40500921 | |
Switchover box up to 30kW_3WR | Connection of 3 Solax | 50A | No | No | 40500920 | |
Switchover box up to 50kW | Connection of 5 Solax (varies by Austrian federal state) | 100A | N/A | N/A | 40500908 | |
to |
|
|
|
|
|
|
40500912 |
|
|
|
|
|
|
Switchover box 1x Solax FRT | Connection of 1 Solax | 35A | Yes | Yes | 40800932 | |
Switchover box 2x Solax FRT | Connection of 2 Solax | 35A | Yes | Yes | 40800933 |
Systems with Sofar inverter (UPS)
Name | Info | Max. grid connection | Backup power 100mA RCD integrated | FRT-capable? | Part number | Link |
(for AT) |
|
|
|
|
|
|
Switchover box UPS up to 20 kW | Connection of 1 Sofar 10, 15, or 20 kW | 35A | Yes | No | 40800930 | |
Switchover box UPS FRT up to 20 kW | Connection of 1 Sofar 10, 15 or 20 kW | 35A | Yes | Yes | 40800931 |
Please report further sizes and configurations to the product team. Implementation will be reviewed accordingly!