Home storage › Smart meters & meters

Solax | CHINT DTSU666-CT current transformer measurement

Updated on 20/11/2026

This article supplements selected chapters of the manual but does not replace it. Read the manual in full, especially regarding the qualifications required as a qualified electrician, hazard warnings and protective equipment. You can find it under "Links" in the table of contents.

Table of contents

Overview

Use: Solax hybrid inverter Communication type: ModBus RTU Phase netting: non-netting Measurement method: current transformer measurement MID certified: no Article number set (meter + CTs): 40620798 Article number meter: not available Article number CT: 40800669

CHINT DTSU666-CT current transformer measurementSolax | CHINT DTSU666-CT current transformer measurement – Abbildung 2
Solax | CHINT DTSU666-CT current transformer measurement – Abbildung 3Solax | CHINT DTSU666-CT current transformer measurement – Abbildung 4

Manuals:

Electrical installation

Solax CT measurement

The arrow on the current transformers must point towards the CUSTOMER (= LOADS).

Communication connection

Inverter

CHINT

A+

1

24

B-

2

25

GND

Solax | CHINT DTSU666-CT current transformer measurement – Abbildung 6

CT ratio

Article number

200A/5A = 40

40800669

Configuration

The CT ratio must be set differently for different current transformer clamps. neoom supplies current transformers with a ratio of 200A / 5A = 40

However, you do not have to use the current transformer clamps supplied by neoom. The ratio may therefore differ.

Caution: Do not extend or shorten the cables of the current transformer clamps.
Solax | CHINT DTSU666-CT current transformer measurement – Abbildung 7

Software/firmware version

The firmware version of the CHINT differs between the CHINT for a Solax and the CHINT for a Sofar

Error code/ troubleshooting

Energy meter transmits unrealistic values

Check whether the reference voltage L1, L2, L3 (power supply for the energy meter) matches the phases measured by the respective current transformer. To do this, switch off the storage system and the PV system and observe the grid consumption of the installation. If unrealistic values are transmitted on different phases, this indicates an incorrect connection. 3-phase busbars are often used during installation, which can easily lead to this error.

FAQs

How does an incorrectly installed energy meter affect the storage system?

What typical signs indicate that the energy meter was not installed correctly?

What happens if a charging station or an external inverter is installed upstream of the energy meter, and how does this incorrect installation affect CONNECT?

More on Battery storage

Solax | CHINT DTSU666-CT CT measurement | neoom