The Solax inverter of a KJUUBE or KJUUBE Light reports Bat Volt Fault (battery voltage too low). Check these causes one by one.
1. Follow-up error of a BMS internal error
Check whether a BMS internal error occurred before. In that case the Bat Volt Fault is a follow-up error.
2. Wrong number of battery modules or mixed modules
Check which BMS is installed and whether the number of battery modules fits. Adjust it if needed.
BMS | Modules min. | Modules max. |
|---|---|---|
SC0500 | 4 | 8 |
SC1000 | 6 | 14 |
Do not mix module types: use only H48050 (48 V / 50 Ah) or only H48074 (48 V / 74 Ah). Remove deviating modules and keep the minimum number in mind.
More: Extending battery modules (in German)
3. Coiled cables
The inductance of coiled cables can induce voltage and trigger the error. Uncoil the cables, route them differently or use a shorter cable.
4. Voltage of single modules too low
Measure the voltage of each module. If it is outside the normal values:
- All module status LEDs are green: set the operating mode on the inverter to "charge first" (Laden vorrangig).
- Single status LEDs are red: disconnect the modules with a red LED. Keep the minimum number of modules in mind (see table above).