Bat Volt Fault on the Solax inverter

Updated on 19/11/2026

The Solax inverter of a KJUUBE or KJUUBE Light reports Bat Volt Fault (battery voltage too low). Check these causes one by one.

1. Follow-up error of a BMS internal error

Check whether a BMS internal error occurred before. In that case the Bat Volt Fault is a follow-up error.

2. Wrong number of battery modules or mixed modules

Check which BMS is installed and whether the number of battery modules fits. Adjust it if needed.

BMS

Modules min.

Modules max.

SC0500

4

8

SC1000

6

14

Do not mix module types: use only H48050 (48 V / 50 Ah) or only H48074 (48 V / 74 Ah). Remove deviating modules and keep the minimum number in mind.

More: Extending battery modules (in German)

3. Coiled cables

The inductance of coiled cables can induce voltage and trigger the error. Uncoil the cables, route them differently or use a shorter cable.

4. Voltage of single modules too low

Measure the voltage of each module. If it is outside the normal values:

  • All module status LEDs are green: set the operating mode on the inverter to "charge first" (Laden vorrangig).
  • Single status LEDs are red: disconnect the modules with a red LED. Keep the minimum number of modules in mind (see table above).